ShawFlex VFD cables are the preferred power cables for AC Drives. These cables are primarily used between Pulse Width Modulation (PWM) inverters and AC motors.

Tray cables are suitable for use in raceways, including ventilated, non-ventilated, indoor / outdoor and ladder-type cable trays in wet / dry locations and are applicable in Industrial and Processing facilities.

Voltage

1000V

Optional: 600V / 5000V

Product Construction

  • Insulation:
    • XLPE (RW90 rated)rated: 90°C wet / 105°C dry
    • UV sunlight resistant SUN RES (all colours)
    • Direct burial rated
    • - 40°C cold bend / impact rated
    • Rated for use in hazardous locations:
      • Class I Zone 0 (Intrinsically Safe cables only)
      • Class 1 Zone 1 (Div 1)
      • Class 1 Zone 2 (Div 2)
  • Shielding:
    • Dual helically applied copper tape shield
  • Armour:
    • Aluminum Interlocking Armour (AIA) (standard)
    • Steel Interlocking Armour (SIA) (optional)
  • Jacket:
    • FR LAG PVC (AG14 rated) inner black jacket
    • FR LAG PVC (AG14 rated) outer black or yellow jacket (standard)rated: 90°C to -40°C
  • Available in:
    • Custom insulation / jacket colours
    • LSZH Jacket

Certifications/Compliances

  • CSA C22.2 #131, Teck 90 Cable
  • CSA C22.2 NO. 174, Cables & Cable Glands for use in Hazardous Locations
  • CSA C22.2 #38, Thermoset Insulated Wires &Cables (XLPE)
  • CSA FT4, UL 1685 FT4, Vertical Tray Flame Test rated
  • IEEE 383 & 1202 (70,000 BTU / hr), Vertical Flame Test rated
  • ICEA T-30-520 (70,000 BTU / hr), Vertical Flame Test rated

Colour Coding

  • 3C Black,# Coded

Product Properties

  1. Tri-sectional Grounding Conductors
  2. Stranded Bare (ASTM B8) Annealed Copper Conductors
  3. XLPE (RW90 Rated) Insulated Conductors
  4. Polypropylene Fillers
  5. Polyester Separator Tape
  6. Dual Helically Applied Bare/Tinned Copper Tape Shield
  7. FR LAG PVC Inner Protective Jacket
  8. Aluminum Interlocked Armour (AIA) (standard)
  9. FR LAG PVC Outer Protective Jacket
Part Number Number of Conductors Conductor Size (AWG/MCM) Ground Wire Size
(uninsulated) (AWG/MCM)
OD Over Inner Jacket (in/mm) Nominal Diameters Cable Weight (lbs/1000ft)/ (kg/km) Ampacity (30°C ambient) Max. Pulling Tension (Pulling Eye) (lb/kg) Min. Bend Radius (Pull) (in/mm)
          Over Armour (in/mm) Overall Cable (in/mm)        

8021HM1203007DR

3

12

18

0.503 / 12.78

0.743 / 18.88

0.823 / 20.91

401 / 597

30

157 / 71

14.8 / 376

8021HM1003007DR

3

10

16

0.595 / 15.11

0.835 / 21.21

0.915 / 23.24

544 / 810

40

249 / 113

16.5 / 418

8021HM0803007DR

3

8

14

0.657 / 16.69

0.897 / 22.79

0.977 / 24.82

687 / 1022

55

397 / 180

17.6 / 447

80213M0603007DR

3

6

12

0.801 / 20.35

1.041 / 26.45

1.121 / 28.48

1047 / 1559

75

629 / 285

20.2 / 513

80213M0403007DR

3

4

12

0.942 / 23.94

1.182 / 30.03

1.262 / 32.06

1357 / 2020

95

1002 / 454

22.7 / 577

80213M0203007DR

3

2

10

1.067 / 27.1

1.307 / 33.2

1.387 / 35.23

1809 / 2692

130

1593 / 723

25 / 634

80213M0103407DR

3

1

10

1.237 / 31.42

1.477 / 37.51

1.557 / 39.55

2286 / 3402

145

2009 / 911

28 / 712

80213M1/03407DR

3

1/0

10

1.323 / 33.6

1.563 / 39.7

1.659 / 42.14

2671 / 3975

170

2534 / 1150

29.9 / 758

80213M2/03407DR

3

2/0

10

1.415 / 35.95

1.655 / 42.05

1.751 / 44.48

3104 / 4620

195

3194 / 1449

31.5 / 801

80213M3/03407DR

3

3/0

8

1.525 / 38.74

1.83 / 46.48

1.926 / 48.92

3809 / 5669

225

4007 / 1818

34.7 / 881

80213M4/03407DR

3

4/0

8

1.645 / 41.79

1.95 / 49.54

2.046 / 51.98

4492 / 6685

260

5078 / 2304

36.8 / 936

80213M2503607DR

3

250

8

1.847 / 46.92

2.152 / 54.67

2.248 / 57.11

5328 / 7930

290

6000 / 2722

40.5 / 1028

80213M3503607DR

3

350

6

2.069 / 52.55

2.374 / 60.29

2.494 / 63.34

7008 / 10430

350

8400 / 3810

44.9 / 1140

80213M5003607DR

3

500

6

2.344 / 59.54

2.649 / 67.28

2.769 / 70.33

9214 / 13713

430

12000 / 5443

49.8 / 1266

80213M7503607DR

3

750

6

2.729 / 69.31

3.034 / 77.06

3.168 / 80.46

12906 / 19206

535

18000 / 8165

57 / 1448

*Ampacity value based on Canadian Electrical Code, Version 2015, Table-2.

Market / Applications

  • Energy
  • Industrial
  • Mining
  • Petrochem/Pulp & Paper
  • Water/Waste Water Treatment

Documentation

Version: 01 2018/JAN/02
SEARCH PRODUCT CATALOG   
Need more information? Click here to contact us directly!
Our Success Stories

Our Success Stories

Discover Shawcor integrated services and advanced technologies being applied to the world’s largest projects in the most extreme and challenging environments. Lookup for any project by Geo-location, Capability, Technology and Service provided.

View more success stories
SEND US A MESSAGE