Skip to Content
mobile menu
PIPELINE PERFORMANCE shawcor.com
HomeConnection Systems Product Catalog ​UL Metal Clad Armored AIA Power | Multi-Conductor (600V)

​UL Metal Clad Armored AIA Power | Multi-Conductor (600V)

Metal Clad AIA Power cables are suitable for use in ventilated, non-ventilated and ladder type cable trays, direct burial, raceways and for exposed or concealed wiring in wet, damp or dry locations in -40°C (40°F) environments. Applicable for use in Utilities, Industrial and Commercial applications.-

Voltage

600V

Optional: 2000V

Product Construction

  • Insulation:
    • FR XLPE (XHHW-2 rated) rated: 90°C wet / dry
    • VW-1 rated (optional)
  • Armor:
    • Aluminum Interlocked Armor (AIA) (standard)
    • Steel Interlocked Armor (SIA) (optional)
    • Served Wire Armor (optional)
    • Zetabon (optional)
  • Jacket:
    • FR PVC outer black jacket rated: 90°C to -40°C
    • Thermoset CPE optional)
    • Thermoplastic CPE (optional)
    • Thermoplastic LSZH (optional)
  • Available in:
    • Custom insulation / jacket colours
    • Composite constructions

Certifications/Compliances

  • UL 1569, Metal Clad Cables (MC)
  • UL 44, Thermoset Insulated Wires and Cables
  • UL 1685 / FT4, Vertical Tray Flame Test rated
  • IEEE 1202 / 383 (70,000 BTU / hr), Vertical Flame Test rated
  • ICEA T-30-520 (70,000 BTU / hr), Vertical Flame Test rated
  • XLPE (XHHW-2 rated), 90°C wet / dry
  • UV sunlight resistant SUN RES (all colours) (for CT use)
  • Direct burial rated
  • -40°C cold bend rated
  • Rated for use in hazardous locations:
    • Class I Zone 2 (Div 2)
    • Class II Zone 22 (Div 2)

Colour Coding

  • Black conductors (standard)
  • Optional:
    • Method1 K1 or K2

Product Properties

  1. Grounding / Bonding Conductor
  2. Strand Bare (ASTM B8) Annealed Copper Conductors
  3. FR XLPE (XHHW-2 Rated) Insulated Conductors
  4. Polyester Separator Tape
  5. Aluminum Interlocked Armor (AIA)
  6. FR PVC Outer Protective Black Jacket

 

Part Number

 

Number of Conductors

 

Conductor Size (AWG/MCM)

 

Ground Wire Size (AWG/MCM)

 

Nominal Diameter Overall Cable (in/mm)

 

NominalDiameter Over Armor

 

Cable Weight (lb- s/1000ft)/(kg/km)

 

Ampacity (30°C ambient)

Max. Pulling Tension

(Pulling Eye) (lb/ kg)

 

Min. Bend Radius (Pull)

(in/mm)

2C610U140200709

2

14

14

0.51 / 12.95

0.622 / 15.8

172 / 256

25

66 / 30

11.2 / 284

2C610U120200709

2

12

12

0.546 / 13.87

0.658 / 16.71

206 / 306

30

104 / 47

11.8 / 301

2C610U100200709

2

10

10

0.596 / 15.14

0.708 / 17.98

258 / 383

40

166 / 75

12.7 / 324

2C610U080200709

2

8

10

0.714 / 18.14

0.826 / 20.98

348 / 518

55

265 / 120

14.9 / 378

2C610U060200709

2

6

8

0.792 / 20.12

0.904 / 22.96

456 / 678

75

419 / 190

16.3 / 413

2C610U040200709

2

4

8

0.886 / 22.5

0.998 / 25.35

594 / 885

95

668 / 303

18 / 456

2C610U030200709

2

3

6

0.94 / 23.88

1.052 / 26.72

714 / 1063

115

842 / 382

18.9 / 481

2C610U020200709

2

2

6

0.966 / 24.54

1.078 / 27.38

824 / 1226

130

1062 / 482

19.4 / 493

2C610U010240709

2

1

6

1.084 / 27.53

1.196 / 30.38

993 / 1477

145

1339 / 607

21.5 / 547

2C610U1/0240709

2

1/0

6

1.164 / 29.57

1.276 / 32.41

1174 / 1747

170

1690 / 766

23 / 583

2C610U2/0240709

2

2/0

6

1.25 / 31.75

1.362 / 34.59

1392 / 2071

195

2130 / 966

24.5 / 623

2C610U3/0240709

2

3/0

4

1.352 / 34.34

1.464 / 37.19

1710 / 2544

225

2671 / 1212

26.4 / 669

2C610U4/0240709

2

4/0

4

1.464 / 37.19

1.576 / 40.03

2050 / 3051

260

3386 / 1536

28.4 / 721

2C610U250260709

2

250

4

1.596 / 40.54

1.728 / 43.89

2393 / 3561

290

4000 / 1814

31.1 / 790

2C610U300260709

2

300

3

1.702 / 43.23

1.834 / 46.58

2804 / 4173

320

4800 / 2177

33 / 839

2C610U350260709

2

350

3

1.802 / 45.77

1.934 / 49.12

3180 / 4732

350

5600 / 2540

34.8 / 884

2C610U500260709

2

500

3

2.159 / 54.84

2.291 / 58.19

4492 / 6685

430

8000 / 3629

41.2 / 1047

2C610U140300709

3

14

14

0.541 / 13.73

0.653 / 16.58

192 / 285

25

99 / 45

11.7 / 298

2C610U120300709

3

12

12

0.581 / 14.75

0.693 / 17.6

234 / 348

30

157 / 71

12.5 / 317

*Ampacity value based on National Electrical Code, Version 2017, Table 3-10.15(B)(16).

 

 

Part Number

 

Number of Conductors

 

Conductor Size (AWG/MCM)

 

GroundWireSize (AWG/MCM)

Nominal Diameter Overall Cable (in/mm)

 

NominalDiameter Over Armor

 

Cable Weight (lb- s/1000ft)/(kg/km)

 

Ampacity (30°C ambient)

 

Max.PullingTension (PullingEye)(lb/kg)

Min. Bend Radius (Pull)

(in/mm)

2C610U100300709

3

10

10

0.637 / 16.17

0.748 / 19.01

304 / 453

40

249 / 113

13.5 / 342

2C610U080300709

3

8

10

0.768 / 19.51

0.88 / 22.35

423 / 630

55

397 / 180

15.8 / 402

2C610U060300709

3

6

8

0.854 / 21.7

0.966 / 24.55

563 / 838

75

629 / 285

17.4 / 442

2C610U040300709

3

4

8

0.934 / 23.72

1.046 / 26.57

751 / 1118

95

1002 / 454

18.8 / 478

2C610U030300709

3

3

6

0.972 / 24.69

1.084 / 27.53

901 / 1341

115

1263 / 573

19.5 / 496

2C610U020300709

3

2

6

1.023 / 25.97

1.135 / 28.82

1058 / 1575

130

1593 / 723

20.4 / 519

2C610U010340709

3

1

6

1.149 / 29.19

1.261 / 32.04

1292 / 1923

145

2009 / 911

22.7 / 577

2C610U1/0340709

3

1/0

6

1.235 / 31.38

1.347 / 34.22

1546 / 2300

170

2534 / 1150

24.3 / 616

2C610U2/0340709

3

2/0

6

1.328 / 33.73

1.44 / 36.57

1853 / 2757

195

3194 / 1449

25.9 / 658

2C610U3/0340709

3

3/0

4

1.438 / 36.51

1.549 / 39.36

2285 / 3401

225

4007 / 1818

27.9 / 708

2C610U4/0340709

3

4/0

4

1.558 / 39.57

1.69 / 42.92

2794 / 4158

260

5078 / 2304

30.4 / 773

2C610U250360709

3

250

4

1.7 / 43.17

1.832 / 46.53

3232 / 4809

290

6000 / 2722

33 / 837

2C610U300360709

3

300

3

1.814 / 46.07

1.946 / 49.42

3798 / 5652

320

7200 / 3266

35 / 890

2C610U350360709

3

350

3

2.022 / 51.37

2.154 / 54.72

4528 / 6738

350

8400 / 3810

38.8 / 985

2C610U500360709

3

500

3

2.298 / 58.36

2.459 / 62.47

6206 / 9236

430

12000 / 5443

44.3 / 1124

2C610U140400709

4

14

14

0.574 / 14.58

0.686 / 17.42

217 / 323

20

132 / 60

12.3 / 314

2C610U120400709

4

12

12

0.618 / 15.71

0.73 / 18.55

269 / 400

24

209 / 95

13.1 / 334

2C610U100400709

4

10

10

0.68 / 17.28

0.792 / 20.13

349 / 520

32

332 / 151

14.3 / 362

2C610U080400709

4

8

10

0.827 / 21

0.939 / 23.85

502 / 747

44

529 / 240

16.9 / 429

2C610U060400709

4

6

8

0.922 / 23.43

1.035 / 26.28

679 / 1011

60

839 / 380

18.6 / 473

2C610U040400709

4

4

8

1.003 / 25.48

1.115 / 28.32

922 / 1372

76

1336 / 606

20.1 / 510

2C610U030400709

4

3

6

1.07 / 27.18

1.182 / 30.03

1115 / 1660

92

1684 / 764

21.3 / 540

2C610U020400709

4

2

6

1.147 / 29.13

1.259 / 31.98

1329 / 1978

104

2124 / 964

22.7 / 576

2C610U010440709

4

1

6

1.263 / 32.07

1.375 / 34.92

1625 / 2418

116

2678 / 1215

24.7 / 629

2C610U1/0440709

4

1/0

6

1.359 / 34.52

1.471 / 37.37

1954 / 2908

136

3379 / 1533

26.5 / 673

2C610U2/0440709

4

2/0

6

1.463 / 37.16

1.575 / 40

2359 / 3510

156

4259 / 1932

28.3 / 720

2C610U3/0440709

4

3/0

4

1.586 / 40.28

1.718 / 43.63

2953 / 4395

180

5343 / 2423

30.9 / 785

2C610U4/0440709

4

4/0

4

1.721 / 43.7

1.853 / 47.06

3585 / 5335

208

6771 / 3071

33.3 / 847

2C610U250460709

4

250

4

1.981 / 50.31

2.113 / 53.66

4335 / 6451

232

8000 / 3629

38 / 966

2C610U300460709

4

300

3

2.108 / 53.55

2.24 / 56.91

5084 / 7566

256

9600 / 4355

40.3 / 1024

2C610U350460709

4

350

3

2.229 / 56.61

2.361 / 59.97

5804 / 8637

280

11200 / 5080

42.5 / 1079

2C610U500460709

4

500

3

2.537 / 64.45

2.699 / 68.56

8002 / 11908

344

16000 / 7258

48.6 / 1234

*Ampacity value based on National Electrical Code, Version 2017, Table 3-10.15(B)(16). Per NEC 310.15(B)(3)(a), the ampacity of 4 / C cable shall be reduced by a factor of 0.8 when the neutral is considered a currrent-carrying conductor.

Market / Applications

  • Civil Construction Projects
  • Commercial Construction Projects
  • Communication Power & Control
  • Communications Cable Splice & Protection
  • Generation
  • Generation - Nuclear
  • Generation - Renewables
  • Generation - Renewables - Geo Thermal
  • Generation - Renewables - Solar
  • Generation - Renewables - Wind
  • Generation - Traditional Power
  • Industrial
  • Industrial Construction/Automation
  • Mining
  • Petrochem/Pulp & Paper
  • Power Distribution
  • Power Distribution - LV
  • Transit
  • Utility
  • Water/Waste Water Treatment

Documentation

Version: 01 2018/JAN/02
SEARCH PRODUCT CATALOG   
Need more information?
Our Success Stories

Our Success Stories

Discover Shawcor integrated services and advanced technologies being applied to the world’s largest projects in the most extreme and challenging environments. Lookup for any project by Geo-location, Capability, Technology and Service provided.

View more success stories
SEND US A MESSAGE